You have arrived on the Request for Quote (RFQ) page for part number PP400-6-4, a Bauer Inc component that is listed with the product description “Circuitbreaker” and NSN 5925-00-620-5854 for fast identification. By using the form supplied below, you can offer details regarding your requirements to secure customized procurement solutions for your consideration. As our goal is to provide quick service, you can expect a response within 15 minutes of our staff members reviewing your submission. Alternatively, if you use the email or phone number at the bottom of the webpage, you can directly connect with our experts to discuss your needs.
Note : We Will Not Share Your Information To Any Third Parties.
Alongside Bauer Inc part number PP400-6-4, you can seamlessly search for more items from this manufacturer or CAGECode 70882 using our curated catalogs. Similarly, we also offer means for locating other products that belong to FSC 5925 Circuit Breakers, which this component falls under having the NSN 5925-00-620-5854. Whether you desire part number PP400-6-4 or other NSN components, you can rest assured that our entire inventory is sourced from reputable manufacturers and suppliers. Bearing this in mind, kick off procurement today to see why so many customers select Aero Defence Solutions as their trusted purchasing hub.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-620-5854 Item PartTypeName: CIRCUIT BREAKER | 5925 | 006205854 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
A | 0 | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
6319482G6L | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 5.000 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.750 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.625 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.688 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.250 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.312 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 4.625 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
CMLP | THREAD QUANTITY PER INCH | 20 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC AND 50.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC AND 125.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 5000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQJX | NOMINAL THREAD SIZE | 0.250 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 210.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.